4 procedure – Weidmuller PTX800A - Configurable counter and totalizer Benutzerhandbuch

Seite 42

Advertising
background image

4

Procedure

Whenthe

displayshows

Action/Description

Put the instrument in setup mode and scroll through the main menu

CALIn_n

Press ì or Å

CAlIn_y

Press

PGM to select Input calibration

InP_LO_=

Connect the multimeter to measure the Input level, then press

PGM

4.00

Set the Input signal to the appropriate value, e.g., 4.00 mA
When you are happy that the Input is correct, press

PGM

Inp_HI_=

After approx 5s the display introduces the next calibration point. Press

PGM

20.00

Set the Input signal to the appropriate value, e.g., 20.00 mA
When you are happy that the Input is correct, press

PGM

dFactor=

Continue with the setup sequence.

Note: Do not remove the power while the save message is on display.

PTX800 analogue output board showing output type jumper locations.

Link both pairs
of posts for
voltage outputs