41053-363-01
DIR 41053-363 (Version 04)

(4)

Contact Status
Etat des contacts
Kontaktstatus
Estado del contacto

Closed

Open

Open

Open

Open

Closed

Tripped

Test

Normal

95

97

98

96

97

95

98

96

97

95

98

96

97

95

98

96

Situação de contato
Stato dei contatti

95

L2

L3

13

L1

14

A1

A2

T2

T3

T1

96

97

98

T1

T3

T2

S.C.P.D.

1

95

3

5

13

1

14

A1

A2

4

6

2

96

97

98

U

W

V

S.C.P.D.

1

Wiring Diagram - 3 Phase Full Voltage DOL Starter
Schéma de câblage - Pleine tension triphasée Démarreur DOL (direct en ligne)
Verkabelungsschema - 3-phasiger Vollspannungs-DOL-Motoranlasser
Diagrama de cableado - Arrancador DOL (directo en línea) trifásico de voltaje pleno
Diagrama de circuito - Dispositivo de partida DOL, trifásico, de máxima tensão
Schema elettrico - Avviatore diretto trifase a tensione piena

1

1

Connection must be
fitted by user

Connexion à régler par
l'utilisateur

Verbindung muß vom
Benutzer hergestellt werden

La conexión debe ser
realizada por el usuario

Conexão deve ser colocada
pelo usuário

Il collegamento deve essere
adattato dall'utente

1

1

1

1

1

1

Terminal Screw

M3

0.5 … 2.5 mm²

0.55 Nm

0.2 … 0.75 mm²

0.55 Nm

0.5 … 4 mm²

0.55 Nm

0.2 … 1.5 mm²

0.55 Nm

24 … 10 AWG

5 lb-in

22 … 16 AWG

5 lb-in

0.6 x 3.5 mm

1x

2x

1x

2x

1x

2x

#1

Control Connections
Bornes de Commande
Steueranschlüsse
Morsetti di Commando
Conexões de controle
Conexiones de Control

Terminal Screw

M8

4 … 35 mm²

4 Nm

1x

2x

1x

2x

1x

2x

4 … 25 mm²

4 Nm

4 … 50 mm²

4 Nm

4 … 35 mm²

4 Nm

12 … 1 AWG

35 lb-in

8 … 2 AWG

35 lb-in

--

--

4 mm

FOR MULTIPLE CONDUCTOR APPLICATIONS THE SAME SIZE AND STYLE WIRE MUST BE USED.
POUR LES APPLICATIONS A CONDUCTEURS MULTIPLES, UTILISEZ UN CABLE DE MEME TAILLE ET DE MEME STYLE.
BEI VERWENDUNG MEHRERER LEITER MUSS DIESELBE DRAHTSTÄRKE UND DRAHTART VERWENDET WERDEN.
PER PIÙ CONDUTTORI È NECESSARIO UTILIZZARE LE STESSE DIMENSIONI E TIPI DI CAVO.
PARA CONDUTORES DIVERSOS, UTILIZE O MESMO TIPO E TAMANHO DE FIO.
EN APLICACIONES CON MÚLTIPLES CONDUCTORES DEBE UTILIZARSE CABLE DEL MISMO TAMAÑO Y ESTILO.

Main Connections
Raccordements Principale
Hauptanschlüssse
Collegamenti Principale
Conexões principais
Conexiones Principales

Rated Insulation Voltage (Ui):
Rated Operational Voltage (Ue) IEC/UL:
Rated Operating Frequency:

690V AC
690V AC/600V AC
50 / 60 Hz

Rated Insulation Voltage (Ui):
Rated Operational Voltage (Ue) IEC/UL:
Rated Operating Current (Ie):

690V AC
690V AC/600V AC
B600 N.O. / N.C.