Programming scheme – Baumer BE134 Benutzerhandbuch
Seite 15

BE134
www.baumer.com
15
9. Programming scheme
Lines 11-16
Status for line 1-6
0
Parameter can be changed
1
Deletion or input disabled
2
Parameter is skipped
Line 21
Operating modes main counter
0 *
Add. – end signal in case of P2, resetting
to
0
1
Sub. – end signal in case of 0, resetting to
P2
Line 22
Preselection mode
0 *
Main counter 2 preselections (progressive
preselections)
1
Main counter 2 preselections (P1 = trailing
preselections)
2
Main counter with preselection P2, batch
counter with P1
Line 23
Resetting modes
0 *
Main counter and batch counter with auto
reset
1
Main counter without, batch counter with
auto
reset
2
Main counter with, batch counter without
auto
reset
3
Main counter and batch counter without auto
reset
Line 24
Time range and fine scaling for Ph main
counter
0 *
9999.99 s
1
999.59.9 min
2
9999.59 min
3
9999.59 h
Line 25
Time range and fine scaling for totalizer
0 *
same as main counter
1
99999.9 h
Line 26
Indication of the measuring unit on the
display
0 *
without measuring unit
1
h
2
min
3
s
Line 27
Allocation of the lower display
0
without lower display
1
P1 - Preselection value
2 *
P2 - Preselection value
3
tot – Totalizer
4
b - Batch counter
Line 30
Function of the signal inputs A, B
0 *
Time metering while signal A is active/
signal B has no function
1
Count start on signal A. Count stop upon
reaching preselection P2. Count halt during
signal B. Signal A and B pulse edge active.
2
Count start and reset on signal A. Stop and
reset upon reaching preselection P2.
Count halt during signal B. Signal A and B
pulse edge active.
Line 33
Input logic and switching threshold
signal inputs
0 *
PNP Switching threshold 6V
1
NPN Switching threshold 6V
2
PNP Switching threshold 3V
3
NPN Switching threshold 3V
Line 34
Function control input 1 (port 9)