9. Programming scheme

Lines 11-16

Status for line 1-6

0

Parameter can be changed

1

Deletion or input disabled

2

Parameter is skipped

Line 21

Operating modes main counter

0 *

Add. – end signal in case of P2, resetting
to
0

1

Sub. – end signal in case of 0, resetting to
P2

Line 22

Preselection mode

0 *

Main counter 2 preselections (progressive
preselections)

1

Main counter 2 preselections (P1 = trailing
preselections)

2

Main counter with preselection P2, batch
counter with P1

Line 23

Resetting modes

0 *

Main counter and batch counter with auto
reset

1

Main counter without, batch counter with
auto
reset

2

Main counter with, batch counter without
auto
reset

3

Main counter and batch counter without auto
reset

Line 24

Time range and fine scaling for Ph main
counter

0 *

9999.99 s

1

999.59.9 min

2

9999.59 min

3

9999.59 h

Line 25

Time range and fine scaling for totalizer

0 *

same as main counter

1

99999.9 h

Line 26

Indication of the measuring unit on the
display

0 *

without measuring unit

1

h

2

min

3

s

Line 27

Allocation of the lower display

0

without lower display

1

P1 - Preselection value

2 *

P2 - Preselection value

3

tot – Totalizer

4

b - Batch counter

Line 30

Function of the signal inputs A, B

0 *

Time metering while signal A is active/
signal B has no function

1

Count start on signal A. Count stop upon
reaching preselection P2. Count halt during
signal B. Signal A and B pulse edge active.

2

Count start and reset on signal A. Stop and
reset upon reaching preselection P2.
Count halt during signal B. Signal A and B
pulse edge active.

Line 33

Input logic and switching threshold
signal inputs

0 *

PNP Switching threshold 6V

1

NPN Switching threshold 6V

2

PNP Switching threshold 3V

3

NPN Switching threshold 3V






Line 34

Function control input 1 (port 9)