Be134 – Baumer BE134 Benutzerhandbuch
Seite 16

BE134
16 www.baumer.com
0 *
Ph main counter - reset static
1
Ph main counter - reset pulse edge active
2
Ph main counter and totalizer - stop
3
Hold
4
Programming lock
5
Key lock
6
Print (min. pulse duration 30ms)
Line 35
Minimum pulse duration for control input 1
0 *
30 ms
1
100 µs
Line 36
Function control input 2 (port 10)
0
Ph main counter - reset static
1
Ph main counter - reset pulse edge active
2 *
Ph main counter and totalizer – stop
3
Hold
4
Programming lock
5
Key lock
6
7
ext. counting input for batch counter
Line 37
Function control input 3 (port 11)
0 *
tot Totalizer - reset static
1
tot Totalizer - reset pulse edge active
2
b Batch counter - reset static
3
b Batch counter - reset pulse edge active
4
Programming lock
5
Key lock
6
7
ext. counting input for batch counter
Line 38
Taking over of the preselections P1, P2
0 *
Effective immediately after input
1
Not effective until the counter has been
reset
Line 40
Output logic
0 *
Both outputs as make contacts
1
P1 break contact, P2 make contact
2
P1 make contact, P2 break contact
3
Both outputs as break contacts
Line 41
Pulse signal duration P1
0.01
Minimum signal duration
0.25 * Default
99.99
Maximum signal duration
Latch
Permanent signal (by pressing the key C)
Line 42
Pulse signal duration P2
0.01
Minimum signal duration
0.25 * Default
99.99
Maximum signal duration
Latch
Permanent signal (by pressing the key C)
Line 50
Code setting
0000 * Code not active
:
9999
Line 51
Baud rate
0 *
4800 baud
1
2400 baud
2
1200 baud
3
600 baud
Line 52
Parity
0 *
Even parity
1
Odd parity
2
No parity
Line 53
Stop bits
0 *
1 Stop bit
1
2 Stop bits
Line 54
Address
00 *
Default
00
Min.
99
Max.