Selecting a ups, Calculating volt-amperage requirements, Ups transition time – Extreme Networks 12800 Series Benutzerhandbuch

Seite 55: Dc power requirements

Advertising
background image

Meeting Power Requirements

BlackDiamond 12800 Series Switches Hardware Installation Guide

55

In addition, some UPS devices or UPS plus software combinations provide the following functions:

●

Automatically shut down equipment during long power outages.

●

Monitor and log power supply status.

●

Display the voltage (current draw) of the equipment.

●

Restart equipment after a long power outage.

●

Display the voltage currently on the line.

●

Provide alarms on certain error conditions.

●

Provide short-circuit protection.

Selecting a UPS

To determine UPS requirements for your switch, answer these questions:

●

What are the amperage requirements?

●

What is the longest potential time period that the UPS would be required to supply backup power?

●

Where will the UPS be installed?

●

What is the maximum transition time that your installation will allow?

NOTE

Extreme Networks recommends that you use a UPS that provides online protection.

Calculating Volt-Amperage Requirements

To determine the minimum volt-amperage requirements for your UPS:

1

Locate the voltage and amperage requirements for each piece of equipment. These numbers are
usually located on a sticker on the back or bottom of your equipment. Then multiply the numbers
together to get Volt-Amperes (VA):

VA = Volts x Amperes

2

Add the VA from all the pieces of equipment together to find the total VA requirement.

To determine the minimum volt-amperage requirements for your UPS, we recommend that you add
30% to the total.

UPS Transition Time

Transition time is the time that is necessary for the UPS to transfer from utility power to full-load
battery power. For Extreme Networks products, a transition time of less than 20 milliseconds is required
for optimum performance.

DC Power Requirements

This system should be installed in a DC-I battery return configuration. In a DC-I configuration, the
battery return conductor should be connected directly to the central office power return bus, and not to
the equipment frame or the grounding means of the equipment.