Proline Promass 80 PROFIBUS PA

Wiring

31

a0002593

Fig. 22:

Connecting the transmitter, cable cross-section: max. 2.5 mm² (AWG 14)

A

View A (field housing)

B

View B (stainless steel field housing)

C

View C (wall-mount housing)

a

Connection compartment cover

b

Cable for power supply: 85 to 260 V AC, 20 to 55 V AC, 16 to 62 V DC
Terminal No. 1: L1 for AC, L+ for DC
Terminal No. 2: N for AC, L

− for DC

c

Ground terminal for protective earth

d

Fieldbus cable:
Terminal No. 26: PA + (with reverse polarity protection)
Terminal No. 27: PA – (with reverse polarity protection)

e

Ground terminal for fieldbus cable shield
Observe the following:
– the shielding and grounding of the fieldbus cable

→ Page 28

– that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible

f

Service adapter for connecting service interface FXA193 (Fieldcheck, FieldCare)

d

c

e

b

27

25

23

21

2
1

26

24

22

20

L1 (L+)

PA +

N (L-)

PA –

f

PA –

PA +

1

2

c

e

f

b

d

22 23

20 21

24 25 26 27

L1 (L+)

N (L–)

C

a

d

b

a

A

B

d

b

d

b

Advertising