Proline Promass 80 PROFIBUS PA

Commissioning

55

Assignment of the measured variables to the AI module

The AI module can transmit different measured variables to the PROFIBUS master (Class 1).
The measured variables are assigned to the Analog Input function blocks 1 to 4 by means of the local
display or with the aid of an operating program (e.g. FieldCare) in the CHANNEL function:

COMMUNICATION

→ BLOCK SELECTION: select an Analog Input function block →

CHANNEL: select a measured variable

Possible settings

Factory setting:

Example:

You want to cyclically transmit the mass flow to the PROFIBUS master (Class 1) by means of the
Analog Input function block 1 (module AI, slot 1) and the temperature by means of the Analog Input
function block 2 (module AI, slot 2).

1.

COMMUNICATION

→ BLOCK SELECTION: select ANALOG INPUT 1, then select

CHANNEL = MASS FLOW

2.

COMMUNICATION

→ BLOCK SELECTION: select ANALOG INPUT 2, then select

CHANNEL = TEMPERATURE

Measured variable

ID for CHANNEL function

MASS FLOW

277

VOLUME FLOW

273

CORRECTED VOLUME FLOW

398

DENSITY

281

REFERENCE DENSITY

402

TEMPERATURE

285

Module

Analog Input

function block

Measured variable

Unit

ID for CHANNEL

function

AI (slot 1)

1

MASS FLOW

kg/s

277

AI (slot 2)

2

VOLUME FLOW

m/h

273

AI (slot 3)

4

DENSITY

kg/l

281

AI (slot 4)

6

TEMPERATURE

K

285