35

WIKA operating instructions process transmitter, model UPT-2x

14068347.01 06/2014 GB/D

GB

9. Configuration via display and operating unit

9.3 Scaling the measuring range

“Scale setting” defines the start and end of the measuring range.

9.3.1 Performing a wet adjustment

For the start of the measuring range and end of the measuring range, the values will be

taken from the running measurement. The respective output signal can be adjusted.

Requirement Measurement must be running.

Setting range Start of measuring range: -10 ... +110 % of measuring range

End of measuring range: 1 ... 120 % of measuring range

Max. turndown: 100 : 1 (recommended max. 20 : 1)

1. Open the operating menu with [↵].

Select “Basic setting” and confirm with [↵].

2. Select “Scale setting” and confirm with [↵].

3. Select “Wet adjustm.” and confirm with [↵].

4. Define the current measured value as start of

measuring range or end of measuring range:

To define as start of measuring range:

Confirm “min. adjustm.” with [↵].

To define as end of measuring range:

Confirm “max. adjustm.” with [↵].

5. Change digit using [▲] [▼] and confirm with [↵]. The

cursor moves to the next digit. Repeat for each digit.

When the last digit is exited, the menu moves back

to step 2.

With the input of current values that are

not either 4 mA or 20 mA, the pressure

value is converted into the standardised

current signals as soon as the current

value entered is accepted.