Mounting correction (offset), Performing a wet adjustment, Performing a dry adjustment – WIKA UPT-21 Benutzerhandbuch

Seite 38: Gb 9. configuration via display and operating unit

Advertising
background image

38

WIKA operating instructions process transmitter, model UPT-2x

14068347.01 06/2014 GB/D

GB

9. Configuration via display and operating unit

9.5 Mounting correction (offset)

9.5.1 Performing a wet adjustment

Zero point will be taken from measurement in operation.

Requirement

Deviation ≤ 20 % of the measuring range.

Absolute vacuum with absolute pressure measuring instruments.

Not to be carried out without suitable equipment.

1. Open the operating menu with [↵].

Select “Basic setting” and confirm with [↵].

2. Select “Application” and confirm with [↵].

3. Select “Pressure” and confirm with [↵].

4. Select “Mounting corr.” and confirm with [↵].

5. Select “apply” and confirm with [↵].

Current measured value will be used as the new zero

point.

9.5.2 Performing a dry adjustment

The mounting correction is registered manually via the dry adjustment. For all future

measurements, the mounting correction will be subtracted.

Requirement Deviation ≤ 20 % of the measuring range.

1. Open the operating menu with [↵].

Select “Basic setting” and confirm with [↵].

2. Select “Application” and confirm with [↵].

3. Select “Pressure” and confirm with [↵].