9. Configuration via display and operating unit

4. Select “Mounting corr.” and confirm with [↵].

5. Select “change” and confirm with [↵].

6. Change digit using [▲] [▼] and confirm with [↵]. The

cursor moves to the next digit. Repeat for each digit.

Entered value will be used as the new zero point.

9.6 Setting the damping

The damping prevents the fluctuation of the output signal when there are short-term

fluctuations in the measured value.

Pressure spikes will still be registered, e.g. as P

max

in the menu point

“Diagnostics”.

Setting range: 0 ... 99.9 s
1. Open the operating menu with [↵].

Select “Basic setting” and confirm with [↵].

2. Select “Damping value” and confirm with [↵].

3. Change digit using [▲] [▼] and confirm with [↵]. The

cursor moves to the next digit. Repeat for each digit.

Damping is set.