WIKA TR10-A Benutzerhandbuch

Seite 16

Advertising
background image

3345267.12 01/2014 GB/D

16

WIKA operating instructions RTD and TC, intrinsically safe designs (Ex i)

GB

Store the instrument in its original packaging in a location that fulfils the conditions listed above. If

the original packaging is not available, pack and store the instrument as described below:

1. Wrap the instrument in an antistatic plastic film.

2. Place the instrument, along with shock-absorbent material, in the packaging.

3. If stored for a prolonged period of time (more than 30 days), place a bag, containing a

desiccant, inside the packaging.

WARNING!

Before storing the instrument (following operation), remove any residual media. This

is of particular importance if the medium is hazardous to health, e.g. caustic, toxic,

carcinogenic, radioactive, etc.

6. Commissioning, operation

WARNING!

When the thermometer is mounted, the temperature must not drop below the allowed

operating temperature (environment, medium) or exceed it, even when taking

convection and heat radiation into account!

WARNING!

Thermometers must be earthed if dangerous voltages could be expected at the

connection wires (caused, for example, by mechanical damage, electrostatic

discharge or induction)!

6.1 Electrical connection

CAUTION!

Damage to cables and wires, and to connection points, must be avoided

Provide finely stranded conductor ends with end splices (cable assembly)

Both the internal capacitance and inductance must be considered

For the electrical connections of thermometers (e.g. connection circuit diagrams, tolerance values,

etc.), please refer to the appropriate data sheets. If head transmitters or digital displays have been

built into the connection housing, these data sheets must also be given proper consideration.

5. Transport, packaging and storage / 6. Commissioning, operation