15 Error messages
54
0008
reserved
-
0009
Checksum of calibration data
The device must be repaired by JUMO.
h
Send in the device.
v
Chapter 2.1 „Service addresses“
0010
Checksum of configuration data
0011
Registry error
h
Use the Reset key (press >3sec) to acknowledge
0012
RAM error
h
Use the Reset key (press >3sec) to acknowledge
0013
ROM error
The device must be repaired by JUMO.
h
Send in the device.
v
Chapter 2.1 „Service addresses“
0014
Program sequence error occurred
h
Use the Reset key (press >3sec) to acknowledge
0015
Watchdog reset occurred
h
Use the Reset key (press >3sec) to acknowledge
0016
Overvoltage
Secondary voltage too high
h
Measure the level of the mains voltage.
h
Use the Reset key (press >3sec) to acknowledge
Error display (Err)
Cause
Remedy