7 configuration level – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch

Seite 95

Advertising
background image

7 Configuration level

33

2014-06-12

k

ex-factory

Scaling end for analog output

-1999 ... 100 ... 9999

Behavior of the analog output in the event of a malfunction

If an allocated measured value oInP is exceeded or gone below, or if a probe
break or short-circuit occurs, it is switched to an alternative value.

it depends on the set signal type and can be set to fix current and voltage values
using 0 and 1.

0, 1

Type of signal Setting 0

Setting 1

0: 4 ... 20 mA

3.4 mA

22 mA

1: 0 ... 20 mA

0 mA

22 mA

2: 2 ... 10 V

1.7 V

10.7 V

3: 0 ... 10 V

0 V

10.7 V

Analog output

Value range
(factory-setting bold)