7 Configuration level
33
k
ex-factory
Scaling end for analog output
-1999 ... 100 ... 9999
Behavior of the analog output in the event of a malfunction
If an allocated measured value oInP is exceeded or gone below, or if a probe
break or short-circuit occurs, it is switched to an alternative value.
it depends on the set signal type and can be set to fix current and voltage values
using 0 and 1.
0, 1
Type of signal Setting 0
Setting 1
0: 4 ... 20 mA
3.4 mA
22 mA
1: 0 ... 20 mA
0 mA
22 mA
2: 2 ... 10 V
1.7 V
10.7 V
3: 0 ... 10 V
0 V
10.7 V
Analog output
Value range
(factory-setting bold)