7 Configuration level

31

2014-06-12

7.11 C 120 Limit value for relay alternations

7.12 C 121 Counter reading for relay alternations

Value range
(factory-setting bold)

Limit value for relay alternations

Here, the limit value for admissible relay alternations is set.
If the counter reading for relay alternations (C121) exceeds the limit value, er-
ror message 0001 appears immediately and the relay output K1 drops out.

This function is factory-set to "0" and thus inactive.

0 ... 9999

Value range
(factory-setting bold)

Counter reading for relay alternations

Here, the alternations for relay output K1 are counted.
If the limit value set below C120 is reached,
error message 0001 appears and relay output K1 drops out.

The counter is factory-set to "0".

If this error is acknowledged by pressing the

key >3sec, counting is started

again with 0.

0 ... 9999