11 c 120 limit value for relay alternations, 12 c 121 counter reading for relay alternations, 7 configuration level – JUMO 14597 safetyM TB/TW08 Temperature Limiter and Temperature Monitor Operating Manual Benutzerhandbuch
Seite 93
7 Configuration level
31
7.11 C 120 Limit value for relay alternations
7.12 C 121 Counter reading for relay alternations
Value range
(factory-setting bold)
Limit value for relay alternations
Here, the limit value for admissible relay alternations is set.
If the counter reading for relay alternations (C121) exceeds the limit value, er-
ror message 0001 appears immediately and the relay output K1 drops out.
This function is factory-set to "0" and thus inactive.
0 ... 9999
Value range
(factory-setting bold)
Counter reading for relay alternations
Here, the alternations for relay output K1 are counted.
If the limit value set below C120 is reached,
error message 0001 appears and relay output K1 drops out.
The counter is factory-set to "0".
If this error is acknowledged by pressing the
key >3sec, counting is started
again with 0.
0 ... 9999