7 Configuration level
32
7.13 C 122 Operating hour counter
7.14 oInP, oSiG, oSCL, oSCH, oErr for analog output
Value range
(factory-setting bold)
Operating hour counter
The counter adds the operating hours up, during which the device was connect-
ed to the voltage supply.
This counter cannot be acknowledged and displays:
- from 10000 to 10999 hours "10t“,
- from 11000 to 11999 hours "11t“, etc.
Counting ends with "65t" (65535 hours, approx. 7.5 years).
0 ... 65535
Analog output
Value range
(factory-setting bold)
Measured value to be put out on the analog output
0: Difference
1: Inp
2: In2
0, 1, 2
Type of signal
0: 4 ... 20 mA
1: 0 ... 20 mA
2: 2 ... 10 V
3: 0 ... 10 V
0, 1 ... 7
Scaling start for analog output
-1999 ... 0 ... 9999
H
Difference or In2 can only be put out when differential
value calculation is set.