7 Configuration level

2014-06-12

32

7.13 C 122 Operating hour counter

7.14 oInP, oSiG, oSCL, oSCH, oErr for analog output

Value range
(factory-setting bold)

Operating hour counter

The counter adds the operating hours up, during which the device was connect-
ed to the voltage supply.

This counter cannot be acknowledged and displays:
- from 10000 to 10999 hours "10t“,
- from 11000 to 11999 hours "11t“, etc.

Counting ends with "65t" (65535 hours, approx. 7.5 years).

0 ... 65535

Analog output

Value range
(factory-setting bold)

Measured value to be put out on the analog output

0: Difference
1: Inp
2: In2

0, 1, 2

Type of signal

0: 4 ... 20 mA
1: 0 ... 20 mA
2: 2 ... 10 V
3: 0 ... 10 V

0, 1 ... 7

Scaling start for analog output

-1999 ... 0 ... 9999

H

Difference or In2 can only be put out when differential
value calculation is set.