3 technical data, 1 general data and operating conditions, Technical data – Lenze M300 Benutzerhandbuch

Seite 30: General data and operating conditions, En 30

Advertising
background image

Technical data

General data and operating conditions

3

EN

30

Lenze ¯ MDKSEMA ¯ 3.0

3

Technical data

3.1

General data and operating conditions

Conformity and approval
Conformity

CE

2006/95/EC

Low−Voltage Directive

2004/108/EC

EMC Directive

EAC

TP TC 004/2011
(TR CU 004/2011)

Relating to the safety of low
voltage equipment

Eurasian conformity
TR CU: Technical regulation of Custom Union

TP TC 020/2011
(TR CU 020/2011)

Electromagnetic
compatibility of technical
products

Approval

UL/CSA

UL 61800−5−1

Industrial Control Equipment, File No. E132659

CSA 22.2 No. 274

CCC

GB Standard
12350−2009

Chinese Compulsory Certificate
"Safety requirements of small−power motors"

Protection of persons and device protection
Enclosure

EN 60529

IP55
IP54 with brake

When ready for operation:
¯

Seal unused bore holes for cable glands by
means of blanking plugs!

¯

Seal unused connectors by means of protection
covers or blanking plugs!

¯

Close and bolt cover!

(Earth) leakage current

EN 61800−5−1

> 3.5 mA AC, > 10 mA DC

Observe regulations and safety instructions!

Total fault current

In TN systems, the following earth−leakage circuit breakers may be used: 30 mA,
type B

Additional equipotential
bonding

M5 thread with terminal at the terminal box for the connection of a 6 mm

2

PE

cable

Insulation of control circuits

EN 61800−5−1

Safe mains isolation: Double/reinforced insulation for digital inputs and outputs

Insulation resistance

EN 61800−5−1

Site altitude

0 ... 2000 m Overvoltage category III

2000 ... 4000 m Overvoltage category II

Short−circuit strength

EN 61800−5−1

Motor

To a limited extent, error acknowledgement
required

Motor holding brake

No

Brake resistor

No

Control terminals

Yes

Earth fault resistance

EN 61800−5−1

Connection:
Motor

To a limited extent, error acknowledgement
required

Brake resistor

No

Protective measures against

¯

Short circuit on the motor side during switch−on and during operation

¯

Motor stalling

¯

Motor overtemperature (I

2

xt monitoring)

Cyclic mains switching

¯

Switching
processes/minute

3

¯

Switching
processes/hour

Max. 20

¯

Pause

Mains switching of three times per minute must be
followed by a pause of 9 min.

Supply conditions
Mains connection

Power system
TT, TN
(with an earthed neutral)

Operation permitted without restrictions

Delta network
(phase earthed)

Operation not permissible.

IT system

Operation not permissible.

Voltage deviations

Voltage dips

EN 61800−3

Short−time mains voltage dips (cf. IEC 61000−2−1) may cause disconnection.

Control connections

Supply

24 V DC (19.2 ... 28.8 V) by safely separated power supply unit (SELV/PELV)

Digital inputs

IEC 61131−2, type 1

24 V DC, input resistance 5.6 k

W

Digital output

IEC 61131−2, type 1

24 V DC, max. 50 mA