4 installation, 1 important notes, Installation – Lenze M300 Benutzerhandbuch

Seite 32: Important notes

Advertising
background image

Installation

Important notes

4

EN

32

Lenze ¯ MDKSEMA ¯ 3.0

4

Installation

4.1

Important notes

{

Danger!

Hazardous electrical voltage
The leakage current to earth (PE) is > 3.5 mA AC or > 10 mA DC.
Possible consequences:
¯ Death or severe injuries when touching the device in the event of an

error.

Protective measures:
Implement the measures required in EN 61800−5−1. Especially:
¯ Fixed installation

– Implement PE connection in compliance with standards.
– Connect PE conductor twice or PE conductor cross−section

³ 10 mm

2

.

¯ Connection with a connector for industrial applications according to

IEC 60309 (CEE):
– PE conductor cross−section

³ 2.5 mm

2

as part of a multi−core supply

cable.

– Provide for suitable strain relief.

(

Stop!

The product contains electrostatic sensitive devices.
Before working in the connection area, the personnel must be free of
electrostatic charge.

(

Stop!

Humidity on the device
At the transitions of cold zones to warm zones, dew or frost formation on
the device may occur.
Possible consequences:
¯ Response of protective measures
¯ Earth fault or destruction of the device.
Protective measures:
¯ Use the device so that there is no dew or frost formation.
If frost or dew has formed on the device:
¯ Switch device to a deenergised state immediately.
¯ Wait with the restart until the device has dried completely.