Safety instructions

Residual hazards

1

40

MA 13.0001 DE-EN DE/EN 2.0

1.2

Residual hazards
Protection of persons
After power-off, the power terminals UL, BR and GND still carry hazardous

voltages for at least 3 minutes!

ƒ

Before working on the controller, check that no voltage is applied to the

power terminals.

ƒ

Always protect the power terminals against contact.

The discharge current to ground (PE) is > 3.5 mA, according to EN 50178.

ƒ

If a fixed installation is required, design the PE conductor with a cable

cross-section of at least 1.5 mm

2

or use a design with double

PE conductor.

Make sure that cables are installed correctly, and that bolted connections and

plug connections are faultless.
Due to the high currents with regard to low-voltage applications,

current-carrying parts can be strongly heated.
Device protection

ƒ

Connect or disconnect all pluggable terminals in a deenergised state only!

ƒ

A cyclic connection and disconnection of the supply voltage can overload

and destroy the input current limitation of the drive controller:

When effecting a cyclic switching of the supply voltage over a longer

period, the period between two switch-on processes at least has to be

one minute!

Motor protection
Drive systems can reach dangerous overspeeds (e.g. setting of high field

frequencies for motors and machines which are not qualified for this purpose):

ƒ

The controllers do not offer any protection against these operating

conditions. Use additional components for this.

Protection of the machine/system
A missing or incorrect resolver adjustment can bring about undefined control

states. The perfect operation is no longer guaranteed.