Advertising
background image

Electrical installation

Voltage supply

4

50

MA 13.0001 DE-EN DE/EN 2.0

4.3

Voltage supply

Stop!

The maximum permissible current loading of the terminal strip X2

is 16 A per terminal. If required, the supply voltage has to be

connected in parallel!

X2 supply voltage
Pin No.

Designation

Value

Specification

1

UL

24 ... 48 V

DC-bus voltage output stage

2

As 1, loop through of the supply to further drives

3

BR

Connection external brake resistor against UL

4

24 V

+24 V / 1.5 A

Control voltage for control section, DOUT0,

DOUT1, DOUT2 and holding brake, max. 1.5 A

5

As 4, loop through of the supply to further drives

6

GND

0 V

Common reference potential for the DC-bus

voltage and control voltage

7

As 6, loop through of the GND potential to

further drives

Terminal data

Max. conductor

cross-section

Tightening torque

Screw drive

Cable

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

7 mm

2.5

12

0.5 ... 0.6

4.4 ... 5.3

Slot 0.6 x 3.5

With wire end

ferrule