Mechanical installation

Important notes

3

44

MA 13.0001 DE-EN DE/EN 2.0

3

Mechanical installation

3.1

Important notes

ƒ

Use the controllers as built-in units only!

ƒ

In case of contaminated cooling air (dust, lints, greases, aggressive gases):

Take suitable preventive measures, e.g. separate air duct, installation of

filters, regular cleaning, etc.

Stop!

Do not install drives on top of each other in the control cabinet!

ƒ

Observe installation clearances!

You can install several controllers next to each other without free space

in a control cabinet.

Ensure unimpeded ventilation of cooling air and outlet of exhaust air!

Allow a free space of 100 mm at the top and at the bottom.

If possible, the rear panel of the drive controller should be provided

with a good thermal connection to the control cabinet wall.

In case of high load and a bad heat dissipation, the drive controller

reduces the drive power, or possibly switches off.

ƒ

Do not exceed the range of the ambient operation temperature specified

in the Technical Data.

ƒ

In case of permanent oscillation or agitation:

Check whether shock absorbers are necessary.

Possible mounting positions:

Vertically on the control cabinet rear panel with mains terminals at the top.