5 control terminals, Control terminals, Electrical installation – Lenze 931ExK10 Benutzerhandbuch

Seite 52

Advertising
background image

Electrical installation

Control terminals

4

52

MA 13.0001 DE-EN DE/EN 2.0

4.5

Control terminals

X5 inputs and outputs
Pin No.

Signal

Function

Specification

Lenze

Alternatively

adjustable via SDC

1

+AIN0 (DIN0)

Analog input 0

differential

(speed

setpoint,

current

setpoint)

DIN0

Input voltage

-10 V ... +10 V

Overvoltage protection

-30 V ... +30 V

2

-AIN0 (DIN1)

DIN1

Input impedance

> 20 kΩ

Resolution

12 Bit

3

+AIN1 (DIN2)

Analog input 1

differential

DIN2

Offset error

< ± 50 mV

Gain error

< 5 %

4

-AIN1 (DIN3)

DIN3

Limiting frequency

~ 1 kHz

5

+AMON0

Analog monitors

output of internal quantities

(current, speed, etc.)

Output signal

0 V ... 10 V,

max. 2 mA

6

+AMON1

7

GND

Reference potential for pin 1 ... 6,

pin 8 ... 16

8

DIN4

Digital input 4

Rated voltage

+24V DC

9

DIN5

Digital input 5

Voltage range

0 ... +30 V DC

10

DIN6

Digital input 6

HIGH signal

> +8 V DC

11

DIN7

Digital input 7

LOW signal

< +4 V DC

12

DIN8

Digital input 8

Input impedance

> 4.7 kΩ

13

DIN9

Digital input 9

(controller enable / delete error)

Switching delay

(LOW-HIGH transmission)

< 1 ms

14

DOUT0

Digital output 0

(ready for operation)

Output voltage

0 V / 24 V

LOW signal

0 ... 4 V DC

HIGH signal

18 V ... 30 V

15

DOUT1

Digital output 1

Output current

max. 10 mA

Load impedance

> 2.2 kΩ

16

DOUT2

Digital output 2

Switching delay

(LOW-HIGH transmission)

< 1 ms

Terminal data

Max. conductor

cross-section

Tightening torque

Screw drive

Cable

[mm

2

]

[AWG]

[Nm]

[lb-in]

Flexible

7 mm

2.5

12

0.5 ... 0.6

4.4 ... 5.3

Slot 0.6 x 3.5

With wire end

ferrule

Advertising