Technical data – Lenze ELCAMZIxxx4SNNPSNN (LCU 122) Benutzerhandbuch

Seite 50

Advertising
background image

Technical data

Rated data

2

l

50

EDKLCMZ3024−SPS DE/EN 4.0

)

Note!

The motor starters are designed for motor powers between 0.75 kW and 3 kW
and rated currents between 1 A and 7 A.
If motors with powers < 0.75 kW or rated currents < 1 A are operated on the
motor starters, please observe the following:

ƒ

The internal I

2

xt monitoring cannot be used because of the low current.

Switch off the internal I

2

xt monitoring (C0121 = 0).

Use a PTC or thermal contact (NC contact) to monitor the motor
temperature

Appropriate external motor protection switches can be used in addition.

ƒ

The mains phase failure control can respond during operation, although no
main failure has occurred.

Deactivate the mains phase failure control (C0122 = 3) to ensure that the
drive will not switch off with an error message.