Technical data, Rated data, For 20 ms – Lenze ELCAMZIxxx4SNNPSNN (LCU 122) Benutzerhandbuch

Seite 51

Advertising
background image

Technical data

Rated data

2

l

51

EDKLCMZ3024−SPS DE/EN 4.0

I

2

t tripping characteristic:

According to DIN EN 60947−4−2 (AC semiconductor motor controllers and starters)

0.01

0.1

1

10

100

1000

10000

0.02

t [s]

1.05

2

3

4

5

6

7.2

8

I/I

r

Class 10A

Class 10

Class 20

Class 30

start031

Tripping classes

Class 10A

Tripping classes, can be set in C0121

Class 10

= Lenze setting

Class 20
Class 30

I

= Output current

I

r

= Rated motor current, can be set in C0120

Example for
Class 10:

The motor starter shuts down with an error message, if the output current I measures 4 times
the set rated motor current I

r

for approx. 13 s.

)

Note!

Regardless of the tripping class set, the motor starter always shuts down if the
output current I measures 8 times the set rated motor current I

r

for 20 ms.