Electrical installation

Important notes

4

l

54

EDKLCMZ3024−SPS DE/EN 4.0

4

Electrical installation

4.1

Important notes

)

Note!

ƒ

Please keep the plastic covers on the connectors for the control connections
and interfaces!

ƒ

Cover unused connections during transport, storage and operation with the
plastic covers to preserve the certified safety engineering features.

{

Danger!

ƒ

The X2x power connector contacts can conduct hazardous voltages if the
motor starter is connected to the mains. Therefore, disconnect the motor
starter before carrying out any work on it.

ƒ

All control terminals feature only basic insulation (single isolating distance)
following the connection of a PTC thermistor (PTC) or a thermal switch (NC
contact):

Protection against accidental contact with defective isolating distance can
only be ensured through external measures, e.g. double insulation.

ƒ

To avoid injury to persons and breakdowns, it is essential that the motor
starter is properly earthed via X10!

(

Stop!

Ensure trouble−free operation of the motor starter:

ƒ

Avoid compensating currents via the PROFIBUS cable shield:

For this, connect all devices with a 16 mm

2

cable via the FE bolts.

Lay cable in parallel to bus cable.

Use a copper braid cable to connect the FE bolts with the mounting
surface.

ƒ

Properly lock the connector plugs.

EMC−compliant wiring

)

Note!

ƒ

Use a copper braid cable to connect the PE bolt with the mounting surface.

ƒ

Separate control and data cables from motor cables.

ƒ

Connect control and data cable shields at both ends.