2 technical data, 1 general data and operating conditions, Technical data – Lenze ELCAFHIxxx4D34NNPM Highline Benutzerhandbuch

Seite 57: General data and operating conditions, 2technical data

Advertising
background image

Technical data

General data and operating conditions

2

l

57

EDKLCFH3024−XPM DE/EN 6.0

2

Technical data

2.1

General data and operating conditions

General data

Conformity and approval

Conformity

CE

73/23/EEC

Low−Voltage Directive

Protection of persons and devices

Enclosure

EN 60529

IP54

All unused connectors must be covered with plugs or a
protective cover.

Earth leakage current

EN 61800−5−1

> 3.5 mA

Regulations and safety
instructions must be observed!

Total fault current

< 100 mA
The use of residual−current circuit breakers 300 mA is possible
(RCCB, type B).

Equipotential bonding

M6 threaded bolts on housing exterior for connection of a 16
mm

@ protective earth cable

Protective insulation of
control circuits

EN 61800−5−1

Safe isolation from mains by double (reinforced) insulation

Insulation resistance

EN 61800−5−1

Site altitude < 2000 m: Overvoltage category III

Site altitude > 2000 m: Overvoltage category II

Protective measures

Short circuit on the motor side, earth fault when switching on
the mains and during operation, motor overtemperature
(input for PTC or thermal contact, I

2

t monitoring)

Service switch

Design

Rotary switch, triple locking
Feedback contact for status message and reset offault
message (TRIP reset)

Tripping current

16 A (controllers 0,75 ... 3 kW)

25 A (controllers 5 ... 11 kW)

EMC

Noise emission

EN 61800−3

Cable−guided: categoriy C2 with Lenze system cables up to
20 m motor cable length

Noise immunity

EN 61800−3

Category C3

Advertising