Electrical installation – Lenze ELCAFHIxxx4D34NNPM Highline Benutzerhandbuch

Seite 81

Advertising
background image

Electrical installation

Communication

4

l

81

EDKLCFH3024−XPM DE/EN 6.0

Baud rate / bus cable length

Baud rate [kbps]

Length [m]

9.6 − 93.75

1200

187.5

1000

500

400

1500

200

3000 − 12000

100

)

Note!

Ensure that the baud rate depending on the amount of data, cycle time and
number of stations is only selected as high as required for the application.

Specification of the transmission cable

Please follow the specifications of the PROFIBUS user organisation (PUO) for signal cables:

Bus cable specification

Specific resistance

135 − 165

W/km, (f = 3 − 20 MHz)

Capacitance per unit length

£ 30 nF/km

Loop resistance

< 110

W/km

Core diameter

> 0.64 mm

Core cross−section

> 0.34 mm

2

Cores

Double twisted, insulated and shielded