Electrical installation – Lenze ELCAFHIxxx4D34NNPM Highline Benutzerhandbuch

Seite 79

Advertising
background image

Electrical installation

Communication

4

l

79

EDKLCFH3024−XPM DE/EN 6.0

Basic structure of a PROFIBUS network with RS485 cabling without repeater

S

S

S

M

3

3

3

1

2

2

2

0 m

< 1200 m

lcu12x_005

No.

Element

Comment

1

Host

E.g. PC or PLC with PROFIBUS master interface module

2

Bus cable

Adapt baud rate to bus cable length

3

PROFIBUS slave

Device with PROFIsafe on board

)

Note!

If a repeater is used, max. 125 stations can communicate via the PROFIBUS.

Please observe the following when wiring

ƒ

Do not change the bus topology, i.e. do not use stubs.

ƒ

Observe the notes and wiring regulations in the documentation for the control
system.

ƒ

Do not use cables other than specified in the specifications. (

81).

ƒ

Plug bus terminating connector on X32 at the last bus station. Ensure that the
PROFIBUS is also terminated at the first bus station (master).