Electrical installation

Communication

4

l

77

EDKLCFH3024−XPM DE/EN 6.0

4.7

Communication

(

Stop!

High compensation currents
High compensating currents can flow via the PROFIBUS cable shield.
Possible consequences:
Property damage or operational malfunction
Protective measures:
Avoid compensation currents via the PROFIBUS cable shield:

ƒ

Connect all PROFIBUS stations with a 16 mm

2

cable via the PE bolts.

ƒ

Lay this cable in parallel to the bus cable.

ƒ

Use copper braid cable to establish a conductive connection between the PE
bolts and the mounting surface.

lcu94FU_001g

PE

Earthing bolt for compliance with EMC conditions, prevents the flow of compensation
currents via the shield of the PROFIBUS cable

0

16 mm

2

equalizing conductor