Weidmuller PTX800A - Configurable counter and totalizer Benutzerhandbuch

Seite 33

Advertising
background image



Alarmaction

High alarms are active above the setpoint and low alarms are active

below the setpoint. Total alarms are always ‘high’ type, so this setting
is not shown.

Deadband

This parameter sets the “hysteresis” for an alarm channel; the alarm

will clear above or below the setpoint to prevent chatter when the
rate level passes the setpoint. The minimum deadband is one display
count. Total alarms do not need a deadband setting.

Alarmoutputenergisationoptions

There are many applications where it is important to raise an alarm

if the instrument power supply is cut off. Normally energised coil
operation allows for this application.

Alarmtimerdelays

Sets the minimum time that an alarm condition must be present to be

recognised.

Setpointsecurity

You can change the setpoints from the front panel. If you want to

disable this feature, switch on the setpoint security.

Alarmresetsequence

Alarms normally reset automatically when a trip condition has passed.

Manual reset requires the operator to press the appropriate key before
the alarm will clear. The alarm status LED flashes until the alarm is
acknowledged and then remains on until the trip condition is gone.