40

•Calibration

General

The PTX800A analogue outputs and Inputs are calibrated for a specific

range and type. If you have changed the range or type you must follow
the appropriate procedure.

Allow the instrument 15 minutes of powered operation (to reach a

stable temperature) before calibration.

Note: the procedures below shows calibration for the commonly

used 4-0 mA format. If you have chosen another format, the unit will
prompt you with the high and low values you have selected.

Equipmentrequirements
• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)
• Suitable current/voltage source (accurate to 0.05 mV and ±0.1 μA)

OutputCalibration

Terminal Connections for output calibration are:

CalibrationStage

Signaltype

Terminal

Analogue Current Output

mA output +

3

mA output –

4

Analogue Voltage Output

V output +

3

V output –

4