9
Pin
Signal
1
Neutral / –e
Power supply
2
Live / +e
3
Signal +
Analogue output (optional)
4
Signal –
5
0 V
Pulse output
6
Pulse
7
Reset count
Short to 8 to reset count
8
Common
9
Security
Short to 8 for setup mode
10
Input – / 0 V
Inputs (according to set-up) in range:
Current: ±24.00 mA
Voltage: ±11.00 V
11
Input +
12
+24 V DC (out)
13
Normally Closed
Alarm one
(optional)
14
Common
15
Normally Open
16
Normally Closed
Alarm two
(optional)
17
Common
18
Normally Open
The PTX800A input circuits are rated category II (suitable for
measurements performed on the low voltage installation). They may
safely be floating with respect to local ground (i.e., subject to common
mode voltages) up to 50 V DC.
Symbols
The instrument labels use symbols in accordance with IEC61010-1:
- Consult documentation;
- Direct Current;
- Double
Insulated.