Weidmuller PTX800A - Configurable counter and totalizer Benutzerhandbuch

Seite 39

Advertising
background image

9

Pin

Signal

1

Neutral / –e

Power supply

2

Live / +e

3

Signal +

Analogue output (optional)

4

Signal –

5

0 V

Pulse output

6

Pulse

7

Reset count

Short to 8 to reset count

8

Common

9

Security

Short to 8 for setup mode

10

Input – / 0 V

Inputs (according to set-up) in range:
Current: ±24.00 mA
Voltage: ±11.00 V

11

Input +

12

+24 V DC (out)

13

Normally Closed

Alarm one
(optional)

14

Common

15

Normally Open

16

Normally Closed

Alarm two
(optional)

17

Common

18

Normally Open

The PTX800A input circuits are rated category II (suitable for

measurements performed on the low voltage installation). They may
safely be floating with respect to local ground (i.e., subject to common
mode voltages) up to 50 V DC.

Symbols

The instrument labels use symbols in accordance with IEC61010-1:

- Consult documentation;

- Direct Current;

- Double

Insulated.

Connections

Advertising