Inputcalibration, 41 procedure, Terminal connections for input calibration are – Weidmuller PTX800A - Configurable counter and totalizer Benutzerhandbuch

Seite 41

Advertising
background image

41

Procedure

Whenthe

displayshows

Action/Description

Put the instrument in setup mode and scroll through the main menu

CALOut_n

Press ì or Å

CAlOut_y

Press

PGM to select output calibration

Out_LO_=

Connect the multimeter to measure the output level, then press

PGM

4.00

Press

PGM

Measure the output signal

Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press

PGM

Out_HI_=

Press

PGM

20.00

Press

PGM

Measure the output signal

Adjust the output (using the ì or Å keys) until the output is at the value shown
When you are happy that the output is correct, press

PGM

Save

Continue with the setup sequence.

Note: Do not remove the power while the save message is on display.

InputCalibration

Terminal Connections for Input calibration are:

CalibrationStage

Signaltype

Terminal

mA/Voltage Signal Source

Signal +

11

Signal –

10