Commissioning, operation – WIKA M-11 Benutzerhandbuch

Seite 3

Advertising
background image

Circular connector M12 x 1 (4-pin)

2-wire

3-wire

U

B

1

1

0V

3

3

S

+

-

4

Cable outlet, 2 m

2-wire

3-wire

U

B

brown

brown

0V

green

green

S

+

-

white

Angular connector DIN 175301-803 C

2-wire

3-wire

U

B

1

1

0V

2

2

S

+

-

3

5.2 Packaging

Do not remove packaging until just before mounting.

Keep the packaging as it will provide optimum protection

during transport (e.g. change in installation site, sending

for repair).

5.3 Storage

Permissible conditions at the place of storage:

see chapter 3 "Specifications"

Avoid exposure to the following factors:

Proximity to hot objects

Mechanical vibration, mechanical shock (putting it

down hard)

Soot, vapour, dust and corrosive gases

Potentially explosive environments, flammable

atmospheres

Store the instrument in its original packaging in a location

that fulfils the conditions listed above. If the original

packaging is not available, pack and store the instrument

as described below:
1. Wrap the instrument in an antistatic plastic film.

2. Place the instrument, along with the shock-absorbent

material, in the packaging.

3. If stored for a prolonged period of time (more than 30

days), place a bag containing a desiccant inside the

packaging.

WARNING!

Before storing the instrument (following opera-

tion), remove any residual media. This is of

particular importance if the medium is hazard-

ous to health, e.g. caustic, toxic, carcinogenic,

radioactive, etc.

6. Commissioning, operation

CAUTION!

Prior to commissioning, the pressure transmit-

ter must be subjected to a visual inspection.

Leaking fluid is indicative of damage.

Check the diaphragm of the process

connection for any damage.

Only use the pressure transmitter if it is in

perfect condition with respect to safety.

6.1 Mechanical mounting

Spanner flats

Flush diaphragm

(only model M-11)

Sealing

Correct sealing of the process connections with parallel

threads at the sealing face

must be made using suita-

ble flat gaskets, sealing rings or WIKA profile sealings. The

sealing of tapered threads (e.g. NPT threads) is made by

providing the thread with additional sealing material such

as, for example, PTFE tape (EN 837-2).

For further information on sealings see WIKA

data sheet AC 09.08 or under www.wika.com.

6.2 Electrical mounting

The instrument must be grounded via the process

connection!

For instruments with voltage output, use shielded

cable, and, if the cables are longer than 30 m or they

leave the building, earth the shield at least at one end

of the cable.

This is protection class 3 equipment for connection

at low voltages, which are separated from the power

supply or voltage by greater than AC 50 V or DC 120 V.

Preferably, a connection to an SELV or PELV circuit is

recommended; alternatively protective measures from

HD 60346-4-41 (DIN VDE 0100-410). Option for North

America: The connection can be made in line with

"Class 2 Circuits" or "Class 2 Power Units" in accord-

ance with CEC (Canadian Electrical Code) or NEC

(National Electrical Code).

Select a cable diameter that matches the cable gland

of the plug. Make sure that the cable gland of the

mounted plug has a tight fit and that the seals are

present and undamaged. Tighten the threaded connec-

tion and check that the seal is correctly seated, in order

to ensure the ingress protection.

For cable outlets, make sure that no moisture enters at

the cable end.

Remove the protection cap not until shortly before

installation.

Ensure that the diaphragm of the process connection

is not damaged during installation.

The sealing faces at the pressure transmitter and the

measuring point always have to be clean.

Only ever screw in, or unscrew, the instrument via

the spanner flats. Never use the case or the cooling

element as a working surface.

The correct torque depends on the dimensions of the

process connection, the gasket used (form/material)

and the measuring range (see illustration).

When screwing in, do not cross the threads.

For information on tapped holes and welding sockets,

see Technical information IN 00.14 at www.wika.com.

Connection diagrams

For further specifications see chapter 3.5 "Electrical

connection"

Maximum torque
Measuring range ≤ 40 bar: 10 Nm

Measuring range > 40 bar: 20 Nm

Example, model M-11

Parallel thread

Tapered thread

per EN 837

per DIN 3852-E

NPT, R and PT