Operating instructions safety switches cms...as, Function test, Maintenance and inspection – EUCHNER CMSxxxAS1 Benutzerhandbuch
Seite 4: Ec declaration of conformity, Technical data

Operating Instructions Safety Switches CMS...AS
1
EUCHNER GmbH + Co. KG Kohlhammerstraße 16 D-70771 Leinfelden-Echterdingen Tel. +49/711/75 97-0 Fax +49/711/75 33 16 www.euchner.de [email protected]
Subject to technical modifications; no r
esponsibility is accepted for the accuracy of this information. © EUCHNER GmbH + Co. KG
105099-03-10/10 (translation of original operating instructions)
Function Test
f
Close safety guard.
Start the machine.
Machine must stop immediately when the safety
guard is opened!
f
Switch machine off.
Open the safety guard.
The machine must not start when the safety guard
is open!
Maintenance and Inspection
In the event of damage or wear and tear, the
damaged system component must be replaced.
Regularly remove iron shavings on the read head
and actuator.
Only use solvent-free detergents for cleaning the
actuators and read heads!
Figure 3: Dimension drawings of read heads and actuators
The dimensions of the actuators are the same as those of the
read heads, although the former have no connection cable.
CMS-R-AZA-01VL-AS1
CMS-M-AC
CMS-R-BZB-01V-AS1
CMS-M-BH
6
2,5
Sao
1000
45
31,5
2,5
7
67,5
87,5
2,5
13
LED ASI
LED 1
25
6
±0,1
78
5,5
9,5
12
ca.
5,8
2,5
Sao
1000
2,5
7
26,2
19,2
36
22
ca.
5,8
13
5
8,5
4,5
Actuator
Active face
Center offset m at s = 3 mm
Assur
e
d
operating
distance
Actuator
Active face
Center offset m at s
= 3 mm
Assur
ed operating
distance
Regular inspection of the following is necessary
to ensure trouble-free long-term operation:
f
Perfect switching function
f
Secure attachment of the components
f
Loose connections.
f
A function test should be performed at least once
per year.
Shorter intervals may be necessary depending
on the specific application.
Note:The year of manufacture can be seen in the
bottom, right corner of the rating plate.
Exclusion of Liability under the Following
Circumstances
f
Incorrect use
f
Non-observance of the safety instructions
f
Installation and electrical connection not
performed by authorized specialists
f
Function tests not performed
f
Tampering.
EC declaration of conformity
The manufacturer named below herewith declares that
the product fulfils the provisions of the directive(s)
listed below and that the related standards have been
applied.
EUCHNER GmbH + Co. KG
Kohlhammerstrasse 16
70771 Leinfelden-Echterdingen, Germany
Directives applied:
f
Machinery directive 2006/42/EC
Standards applied:
f
EN 60947-5-1:2004 + Cor.:2005 + A1:2009
f
EN 1088:1995+A2:2008
Leinfelden, July 2010
Dipl.-Ing. Michael Euchner
Director
Duc Binh Nguyen
Authorized representative empowered to draw up
documentation
The signed EC declaration of conformity is included
with the product.
Technical Data
Parameter
Value
Read head
Housing material
Reinforced PPS
Ambient temperature
-20 ... +60 °C
Degree of protection
according to EN 60529
IP67
Installation position
Any, alignment with actuator
should be kept in mind
(markings)
Connection type
Connection cable with M12 plug
connector
Cable length
1 m
Cable material
PUR
Method of operation
Magnetic, reed contact
Mechanical life
100 x 10
6
operating cycles
Vibration resistance
10 ... 55 Hz, amplitude 1 mm
Shock resistance
30 g / 11 ms
Actuator
Housing material
Reinforced PPS
Ambient temperature
-20 ... +60 °C
Degree of protection
according to EN 60529
IP67
Installation position
Any, alignment with read head
should be kept in mind
(markings)
Method of operation
Magnetic
Vibration resistance
10 ... 55 Hz, amplitude 1 mm
Shock resistance
30 g / 11 ms
AS-Interface data acc. to
EA code: 7
AS-Interface specification 3.2
ID code: B
Operating voltage AS-Interface DC 26.5 ... 31.6 V
Total current consumption, max.
30 mA
Valid AS-Interface addresses
1 - 31
AS-Interface inputs
In accordance with AS-Interface
Safety at Work
Switch actuated
D0, D1, D2, D3 code sequence
Switch open
D0, D1, D2, D3 zero sequence
AS-Interface outputs
according to AS-Interface Safety
at Work
Output D1
D1 = 1
¨
LED ON
D1 = 0
¨
LED OFF
Distances
with read head
CMS...AZA...
CMS...BZB...
Switch-on distance S
ao
9 mm
7 mm
Assured
Switch-off distance S
ar
70 mm
40 mm
Center offset m between
actuator and read head
± 2.5 mm at a distance of s =
3 mm
Times
Time-delay max.
From state change
5 ms
Reliability figures according to EN ISO 13849-1
Category
3
Performance Level (PL)
e
PFH
d
4.29 x 10
-8
Mission time
20 years