Electrical installation
Voltage supply
4
50
MA 13.0001 DE-EN DE/EN 2.0
4.3
Voltage supply
Stop!
The maximum permissible current loading of the terminal strip X2
is 16 A per terminal. If required, the supply voltage has to be
connected in parallel!
X2 supply voltage
Pin No.
Designation
Value
Specification
1
UL
24 ... 48 V
DC-bus voltage output stage
2
As 1, loop through of the supply to further drives
3
BR
Connection external brake resistor against UL
4
24 V
+24 V / 1.5 A
Control voltage for control section, DOUT0,
DOUT1, DOUT2 and holding brake, max. 1.5 A
5
As 4, loop through of the supply to further drives
6
GND
0 V
Common reference potential for the DC-bus
voltage and control voltage
7
As 6, loop through of the GND potential to
further drives
Terminal data
Max. conductor
cross-section
Tightening torque
Screw drive
Cable
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
7 mm
2.5
12
0.5 ... 0.6
4.4 ... 5.3
Slot 0.6 x 3.5
With wire end
ferrule