5 control terminals, Control terminals, Electrical installation – Lenze 931ExK10 Benutzerhandbuch
Seite 52

Electrical installation
Control terminals
4
52
MA 13.0001 DE-EN DE/EN 2.0
4.5
Control terminals
X5 inputs and outputs
Pin No.
Signal
Function
Specification
Lenze
Alternatively
adjustable via SDC
1
+AIN0 (DIN0)
Analog input 0
differential
(speed
setpoint,
current
setpoint)
DIN0
Input voltage
-10 V ... +10 V
Overvoltage protection
-30 V ... +30 V
2
-AIN0 (DIN1)
DIN1
Input impedance
> 20 kΩ
Resolution
12 Bit
3
+AIN1 (DIN2)
Analog input 1
differential
DIN2
Offset error
< ± 50 mV
Gain error
< 5 %
4
-AIN1 (DIN3)
DIN3
Limiting frequency
~ 1 kHz
5
+AMON0
Analog monitors
output of internal quantities
(current, speed, etc.)
Output signal
0 V ... 10 V,
max. 2 mA
6
+AMON1
7
GND
Reference potential for pin 1 ... 6,
pin 8 ... 16
8
DIN4
Digital input 4
Rated voltage
+24V DC
9
DIN5
Digital input 5
Voltage range
0 ... +30 V DC
10
DIN6
Digital input 6
HIGH signal
> +8 V DC
11
DIN7
Digital input 7
LOW signal
< +4 V DC
12
DIN8
Digital input 8
Input impedance
> 4.7 kΩ
13
DIN9
Digital input 9
(controller enable / delete error)
Switching delay
(LOW-HIGH transmission)
< 1 ms
14
DOUT0
Digital output 0
(ready for operation)
Output voltage
0 V / 24 V
LOW signal
0 ... 4 V DC
HIGH signal
18 V ... 30 V
15
DOUT1
Digital output 1
Output current
max. 10 mA
Load impedance
> 2.2 kΩ
16
DOUT2
Digital output 2
Switching delay
(LOW-HIGH transmission)
< 1 ms
Terminal data
Max. conductor
cross-section
Tightening torque
Screw drive
Cable
[mm
2
]
[AWG]
[Nm]
[lb-in]
Flexible
7 mm
2.5
12
0.5 ... 0.6
4.4 ... 5.3
Slot 0.6 x 3.5
With wire end
ferrule