Runmode – Weidmuller RI4 - Multi channel signal transmitter / display Benutzerhandbuch

Seite 26

Advertising
background image

6

EXIT

Micromann Multi+
RI4 Version 2.05

Alarm Sequence
3 1 2 4

Input1= 56.9ßC
Input2= 13.6ßC

AL1 SP= 100.0ßC
MV In1= 56.9ßC

AL2 SP= 15.0ßC
MV In2= 13.6ßC

A.Out1= 1.72V
MV In3= 129.1ßC

A.Out2
Disabled

Input3= 129.1ßC
Input4= 129.6ßC

2 s

MENU

ENT

EXIT

ENT

Review Mode
Prev Next

Calibration Mode
Prev Next

AL3 SP= 120.0ßC
MV Dif= 116.0ßC

AL4 SP= 100.2ßC
MV In3= 129.1ßC

AL1 SP 100.0ßC
MV In1= 56.9ßC

Raise Setpoint

ENT Save Changes to Setpoint

MENU Accept Alarm 1

EXIT Accept Alarm 4

ENT Select mode

EXIT Return to Run mode

Lower Setpoint

Setup Mode
Prev Next

*Automatic Scrolling only
You can setup the unit to scroll automatical y
through values Input1 thru AO2 or
through the inputs on y (Input1
thru Input4).
Allowed timeouts are from 2 to 20 s.
Manual scrolling (through all the values)
sti l works as shown.

Error Messages

If one or more input wires become
disconnected, the unit will display an error
message:
Open A&B

for Bsense disconnected

Open A

for A disconnected

Open B

for B disconnected

Open A&B

is also shown with no input

connected.

2-20 s*

2-20 s*

2-20 s*

2-20 s*

2-20 s*

2-20 s*

2-20 s*

All Alarms Accepted

Alarm T

rigger

ed

Automatic Accept Mode

Manual Accept Mode*

Accept Alarm 2
Accept Alarm 3

*Alarm LEDs Flash until accepted

Alarms accepted automatically
and unit remains in Run mode

•Runmode

Run mode is the normal operating mode of the RI4. During run

mode the RI4 scans the inputs; calculates internal variables; updates
the display, alarm relay states and analogue outputs; and, if digital
communications are fitted, sends information to the master when
requested. It will also allow setpoint adjustment, acknowledgement
of latched alarms and review of set-up parameters via the front panel
keypad and display.

Parametersettingoverview