Weidmuller RI4 - Multi channel signal transmitter / display Benutzerhandbuch
Seite 33

TerminalConnectionsforoutputcalibration
AnalogueOutputChannel
CalibrationStage
Signaltype
Terminal
Channel One
Current Output
mA output +
15
mA output −
16
Voltage Output
V output +
15
V output −
17
Channel Two
Current Output
mA output +
18
mA output −
19
Voltage Output
V output +
18
V output −
20
Outputcalibrationprocedure
1. Select the channel you wish to calibrate (see diagram above).
. Press ENT, display will show: A.Out1 @ 0.00 mA
. Measure the output current from that channel.
4. Use the
Å
and
ì
keys to adjust the output until it is correct.
5. Press ENT, display will show: A.Out1 @ 20.00 mA
6. Use the
Å
and
ì
keys to adjust the output until it is correct.
. Press ENT, display will show: A.Out1 @ 0.00 V
8. Measure the output voltage from that channel.
9. Use the
Å
and
ì
keys to adjust the output until it is correct.
10. Press ENT, display will show: A.Out1 @ 10.00 V
11. Use the
Å
and
ì
keys to adjust the output until it is correct.
1. At the ‘Continue?’ prompt, select ‘Yes’ to go the next Output
Channel or ‘No‘ to go back to the calibration menu.
1. At the ‘Save?’ prompt, select ‘Yes’ to permanently save the
values or ‘No‘ to use the new values until next power up.