Calibrationmode – Weidmuller RI4 - Multi channel signal transmitter / display Benutzerhandbuch

Seite 31

Advertising
background image

1

CommunicationsSetup

Allows you to configure the RS4/RS485 outputs.

DisplaySetup

Sets up display scrolling options.

ENT

EXIT

EXIT

EXIT

ENT

Calibration Mode
Prev Next

To Run
Mode

Calibrate P.I.N
101

Default PIN = 101

Lower PIN

Calibrate Output
Prev Next

ENT

Calibrate Input
Prev Next

Select which input to calibrate

Previous Output Channel

ENT Ca ibrate Output

Next Output Channel

EXIT Exit

Calibrate
Output 1

Raise PIN

ENT

Input calibration Procedure (see below)

EXIT

MENU

ENT

Invalid PIN
Menu->Retry

•CalibrationMode

General

The RI4 is factory calibrated. Once calibrated it will operate with

any input or output format without calibration. Youshouldnothaveto
calibratetheunitbeforeinstallation.

Allow the instrument 15 minutes of powered operation (to reach a

stable temperature) before calibration.

During calibration allow a few seconds for signals to stabilise before

accepting the value.

Equipment requirements

• A suitable Pt100 RTD Simulator (must be able to simulate Pt100 to

±0.05 % or better accuracy)

• An accurate digital multimeter (accurate to 0.05 mV and ±0.1 μA)