DisplayOperation

The display can be set up to automatically scroll through the various

items of display information or just the input values. Alternatively, you
can set it so that the up and down scroll the display up or down. The
display information shows the input measurements, alarm status and
analogue output signal.

Remoteconfiguration

If the unit has the digital communications option you can configure the

unit using the software provided. If not then you should use the front
panel key pad as described below.

Reviewingthesetup

For review mode, press the MENU key and Press ENT to select Review

mode. To navigate through the menus, use
• the

Å

and

ì

keys to scroll forward or backwards

• the ENT key to select a menu item
• the EXIT key to step out of a menu

Note: You can use review mode while the instrument is in service and

the analogue output, digital communications and alarms will continue
to operate correctly.

Changingthesetup

For setup mode, press the MENU key, scroll the display until it shows
‘Set-up Mode’ and Press ENT to select set-up mode. You will be

asked for a PIN number (the default for set-up is 100). There is a full
description of the setup mode in the following pages.

Clearingtrippedalarms

You can acknowledge a tripped alarm by simply pressing the key

for that channel (below alarm led). The alarm led will flash red for
unacknowledged alarms.