For effective protection from electromagnetic noise, all signal cables
must be shielded, or located on conductive trays or in conduits.

Terminal

Signal

1

24 V DC (out)

Input signals

2

Current +

3

Common −

4

Voltage +

5

Alarm Channel One Inhibit

Alarm inhibit
Signals

6

Alarm Channel Two Inhibit

7

Inhibit Input Common

8

Link to Terminal 1 to change the set-up

Security Link

9

Neutral (−)

Power supply

10

Live (+)

11

Normally Closed

Alarm Channel One

12

Common

13

Normally Open

14

Normally Closed

Alarm Channel Two

15

Common

16

Normally Open

Case

Earthing is via a stud on lower side of case

The double lines represent isolation between circuits

InhibitInputSignals
The alarm inhibit inputs accept voltages. A -0 V signal will prevent
the alarm channel from operating. Voltages >3 V will allow the alarm to
operate normally.