Setupsequence – Weidmuller XFAR - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 23

Advertising
background image

23

•SetupSequence

Setting

Display

Description

Е м

ENT

S/W Version

v1.21

S/W Version 1.21 (Note: this information only applies to versions
1.20 to 1.29)

DisplayandInputs

Input type

IP=1

IP=E

Current (mA)
Voltage (V)

Toggle

Accept

Input range

InL=

4.00

Input range lower limit
e.g., 4.00 mA

-

Dec

-

Inc

Next

Accept

InH=

20.00

Input range upper limit
e.g., 20.00 mA

-

Dec

-

Inc

Next

Accept

Input

Calibration?

CIPn

CIPy

Skip input calibration
Calibrate the inputs

Toggle

Accept

Damping factor

dF=

2

Introduces the damping factor
Value, e.g., 2

-

Dec

-

Inc

Next

Accept

Display range

dP=

.

Decimal point position

-

Shift

Next

Accept

dLO=

0.0

Display range lower limit
e.g., 0.0

-

Dec

-

Inc

Next

Accept

dHI=

100.0

Display range Upper limit
e.g., 100.0

-

Dec

-

Inc

Next

Accept

Alarmchannelone

Coil energisation

A1nE

A1nd

Normally energised
Normally de-energised

Toggle

Accept

Alarm Signal

Proc

rocP

rocn

rocb

Process Measurement
Rate of Change Posititive (Rate of Increase)
Rate of Change Negative (Rate of Decrease)
Rate of Change Both (Rate of Change)

Toggle

Accept

Alarm type

A1=L

A1=H

A1=d

Low type (active below setpoint)
High type (active above setpoint)
Deviation Alarm

Toggle

Accept

Setpoint value

SP1=

50.0

Setpoint value
e.g., 50.0 %

-

Dec

-

Inc

Next

Accept

Deviation value

dv1=

10.0

Introduces deviation value
e.g., 10.0 %

-

Dec

-

Inc

Next

Accept

Deadband value

db1=

0.1

Deadband value
e.g., 0.1 %

-

Dec

-

Inc

Next

Accept