Setup, Alarmoperation – Weidmuller XFAR - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 20

Advertising
background image

20

•Setup

Changingthesetup
For setup mode, connect the security link and press the

Å

and

ì

keys simultaneously. The software version will be displayed (flashing). If
you wish to continue, press within 10 s.
During setup the

Å

and

ì

keys change values and toggle options.

The key accepts changes and moves to the next item in the setup
sequence (see table).
Note: If you remove the security link during the setup sequence, any
changes you have made will be discarded.

•AlarmOperation

Lossofsignalalarms
The loss of signal alarm works with offset zero signals, e.g., -20 mA or
1- V. You program reset and setpoints in the input units.
When the loss of signal occurs both alarm channels are set as for an
alarm condition. The output state will depend on the coil energisation
setting for each channel.

AlarmInhibitInputs
When an alarm inhibit signal is applied the alarm channel is set as if
there was no alarm condition. The output state will depend on the coil
energisation setting for that channel.

Rateofchangealarms
Rate of change alarms are divided into three types: Rate of increase,
Rate of Decrease and Rate of change. A high rate of decrease will
trigger a high type alarm.