Inputcalibrationprocedure

Whenthe

displayshows

Action/Description

ENT

ï

Put the instrument in setup mode and scroll through the main menu

CIPn

Press

Å

or

ì

CIPy

Calibrate inputs?

Start

No

Connect the current source to the inputs (for connections see over page).

I=0

Set the current source to 0.00 mA

Calibrate

Skip

I=5

Set the current source to 5.00 mA

Calibrate

Skip

I=10

Set the current source to 10.00 mA

Calibrate

Skip

I=20

Set the current source to 20.00 mA

Calibrate

Skip

I=50

Set the current source to 50.00 mA

Calibrate

Skip

After the display stops flashing connect the voltage source (for connections see over page).

E=0

Set the Voltage source to 0.00 V

Calibrate

Skip

E=5

Set the Voltage source to 5.00 V

Calibrate

Skip

E=10

Set the Voltage source to 10.00 V

Calibrate

Skip

E=20

Set the Voltage source to 20.00 V

Calibrate

Skip

E=50

Set the Voltage source to 50.00 V

Calibrate

Skip

FnC=

Continue with the setup sequence.

Note: To discard changes to calibration and setup you can remove the power at this point.