Setupsequence(continued) – Weidmuller XFAR - Universal glavanically isolated signal converter Benutzerhandbuch

Seite 24

Advertising
background image

2

Timer delay

dL1=

20

Timer delay

(set to 0 s to disable)

e.g., 20 s

-

Dec

-

Inc

Next

Accept

Alarmchanneltwo

Coil energisation

A2nE

A2nd

Normally energised
Normally de-energised

Toggle

Accept

Alarm type

A2=L

A2=H

Low type (active below setpoint)
High type (active above setpoint)

Toggle

Accept

Setpoint value

SP2=

50.0

Setpoint value
e.g., 50.0 %

-

Dec

-

Inc

Next

Accept

Deadband value

db2=

10.0

Deadband value
e.g., 10.0 %

-

Dec

-

Inc

Next

Accept

Timer delay

dL2=

20

Timer delay

(set to 0 s to disable)

e.g., 20 s

-

Dec

-

Inc

Next

Accept

Generalalarmsettings

Rate Timebase

roc=

sEc

nln

Introduces the timebase
Rate of change in Seconds
Rate of change in Minutes

-

Toggle
Toggle

Next

Accept
Accept

Number of

samples

nS=

10

Introduces the number of samples used for rate
Value, e.g., 10

-

Dec

-

Inc

Next

Accept

Alarm reset

sequence

nOr

rES

Automatic reset
Manual reset

Toggle

Accept

Setpoint

security

SECy

SECn

Setpoints fixed at setup
Can change setpoints

Toggle

Accept

Loss of signal

alarm enable

LSAY

LSAn

Loss of signal alarm enabled
Loss of signal alarm disabled

Toggle

Accept

Loss of signal

setpoint

LSS=

3.5

Introduces loss of signal alarm set point
Value, e.g., 3.50 mA

-

Dec

-

Inc

Next

Accept

Loss of signal

reset point

LSr=

3.5

Introduces loss of signal alarm reset point
Value, e.g., 3.90 mA

-

Dec

-

Inc

Next

Accept

Save values

SAVE

Instrument is saving the changes to the setup and returning to normal
operation

SetupSequence(continued)