Setupsequence(continued) – Weidmuller XFAR - Universal glavanically isolated signal converter Benutzerhandbuch
Seite 24

2
Timer delay
dL1=
20
Timer delay
(set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Alarmchanneltwo
Coil energisation
A2nE
A2nd
Normally energised
Normally de-energised
Toggle
Accept
Alarm type
A2=L
A2=H
Low type (active below setpoint)
High type (active above setpoint)
Toggle
Accept
Setpoint value
SP2=
50.0
Setpoint value
e.g., 50.0 %
-
Dec
-
Inc
Next
Accept
Deadband value
db2=
10.0
Deadband value
e.g., 10.0 %
-
Dec
-
Inc
Next
Accept
Timer delay
dL2=
20
Timer delay
(set to 0 s to disable)
e.g., 20 s
-
Dec
-
Inc
Next
Accept
Generalalarmsettings
Rate Timebase
roc=
sEc
nln
Introduces the timebase
Rate of change in Seconds
Rate of change in Minutes
-
Toggle
Toggle
Next
Accept
Accept
Number of
samples
nS=
10
Introduces the number of samples used for rate
Value, e.g., 10
-
Dec
-
Inc
Next
Accept
Alarm reset
sequence
nOr
rES
Automatic reset
Manual reset
Toggle
Accept
Setpoint
security
SECy
SECn
Setpoints fixed at setup
Can change setpoints
Toggle
Accept
Loss of signal
alarm enable
LSAY
LSAn
Loss of signal alarm enabled
Loss of signal alarm disabled
Toggle
Accept
Loss of signal
setpoint
LSS=
3.5
Introduces loss of signal alarm set point
Value, e.g., 3.50 mA
-
Dec
-
Inc
Next
Accept
Loss of signal
reset point
LSr=
3.5
Introduces loss of signal alarm reset point
Value, e.g., 3.90 mA
-
Dec
-
Inc
Next
Accept
Save values
SAVE
Instrument is saving the changes to the setup and returning to normal
operation
SetupSequence(continued)