Freely programmable monitoring functions when 2 sensors

have been connected (dual sensor)

The following options are not available in the difference

mode!

Redundancy/hot backup:

In the case of a sensor error (sensor break, line resistance too high or

measured value outside the measuring range of the sensor) of one of

the two sensors, the process value will be the value from the working

sensor only. Once the error is rectified, the process value will again be

based on the two sensors, or on sensor 1.
Ageing monitoring (sensor drift monitoring):

An error signal on the output is activated if the value of the

temperature difference between sensor 1 and sensor 2 is higher than

a set value, which can be selected by the user. This monitoring only

generates a signal if two valid sensor values can be determined and

the temperature difference is higher than the selected limit value.

(Cannot be selected for the “Difference” sensor functionality, since the

output signal already indicates the difference value).