10.3.2 Intrinsically safe supply and signal circuit

(4 ... 20 mA loop; terminal und )

Parameters

T32.xS.0IS-x,

T32.xS.0IC-x

T32.xS.0IS-x

T32.xS.0NI

Gas hazardous

application

Dust hazardous

application

Gas hazardous

application

Terminals

+ / -

+ / -

+ / -

Voltage Ui

DC 30 V

DC 30 V

40 V

Strength of current Ii 130 mA

130 mA

23 mA *)

Power Pi

800 mW

750/650/550 mW

1)

1 W

Effective internal

capacitance Ci

7.8 nF

7.8 nF

7.8 nF

Effective internal

inductance Li

100 µH

100 µH

100 µH

*) The maximum operating current is limited by the T32. The maximum output current of the

associated energy-limited apparatus does not have to be ≤ 23 mA.

1) With reference to ambient temperature; see table “Temperature class”.

The supply and signal circuit and the intrinsically safe

sensor circuit must be considered as galvanically

connected to each other.

10.3.3 Connection of the HART

®

modem/HART

®

communicator

(terminal and )

The sum of all voltages connected (supply plus output values

of the HART

®

modem and/or HART

®

Communicator) must not

exceed 30 V for T32.xS.0IS and 40 V for T32.xS.0NI.

The sum of the effective capacitances and inductances must not

exceed the maximum permissible value according to the required

gas group (IIA up to IIC).

11. Maintenance

The temperature transmitter described in these operating instructions

is maintenance-free! The electronics are completely encapsulated

and incorporate no components which could be repaired or replaced.

Repairs must only be carried out by the manufacturer.