Electrical installation

5.1

Important notes

5.1.1

Earth-leakage circuit breaker

Danger!

Dangerous electrical voltage
Drive controllers in this series have an internal mains rectifier. For

this reason, after a short circuit to frame a DC leakage current can

block the leakage current tripping. To prevent this situation, take

the following measures:

ƒ

Connect the system to neutral or use an earth-leakage circuit breaker of

universal-current sensitivity.

Capacitive compensation currents occurring in the cable shield and interference

filter under normal operating conditions can cause the earth-leakage circuit

breaker to trigger incorrectly.

ƒ

Set the trigger current on the earth-leakage circuit breaker sufficiently

high that incorrect triggering is not possible.

Note!

Earth-leakage circuit breakers of universal-current sensitivity are

described in the standards
DIN EN 61800-5-1 and IEC 755.

5.1.2

Electrostatic hazard

Stop!

Electrostatic hazard
Drive controllers in this series contain electrostatic sensitive devices.

Prior to working on the drive controller, service personnel must

discharge themselves.

ƒ

Touch the PE fixing screw or any other earthed metal surface.