Electrical installation

Important notes

Shielding

5

52

EDB712 DE/EN 2.1

5.1.3

Shielding

ƒ

Shield all wires to and from the drive controller.

ƒ

Connect the shield near to the ends of the wires to the central earth wire

connection.

5.1.4

Prevent earth fault

ƒ

Prior to commissioning, ensure there are no connection cables with earth

faults.

5.1.5

Mains potential

Danger!

Dangerous electrical voltage

ƒ

All device terminals carry dangerous mains potential!

Protective measures
All control signals must be safely electrically isolated outside the

drive controller.
Prevent direct contact with the live parts using a protective cover as

double basic insulation.

5.1.6

Setpoint potentiometer

Danger!

Dangerous electrical voltage
If you use the setpoint potentiometer supplied, earth the

mechanical screw fastening, isolate the electrical connections or

cover the connections.

ƒ

On use with a master voltage, remove the setpoint potentiometer and

connect the master voltage to terminal 7 (+) and terminal 8 (-). The

master voltage must be floating and not be referenced to the mains. If

several devices are to be operated on one master voltage, use electrical

isolation.

5.1.7

Switching spike reduction

ƒ

To limit switching spikes that may occur on the operation of a reversing

contactor circuit to initiate reversing of the field, you must connect a zinc

oxide varistor (S20K510, art. no. 307 717) between each of the device

output terminals U-W, V-W and W-U.