Electrical installation

EMC-compliant installation

Installation of a CE-typical drive system

5

55

EDB712 DE/EN 2.1

Shielding

ƒ

Shield all wires from and to the drive controller.

Connect the shield on the motor cable to the mounting plate near the

drive controller using a large area connection. Use earthing clamps on

bare metal mounting surfaces.

Also connect the shields on the cables connected from contactors,

motor protection switches or terminals in the motor cable to the

mounting plate using large area connections.

In the motor terminal box, connect the shield and the motor housing

using a metal cable gland to form a large area connection.

Connect shields on analogue control cables at one end.

Connect the shield on the control cables at both ends to the mounting

plate using a large area connection.

If the mains cable between RFI filter and drive controller together is longer than

300 mm:

ƒ

Shield the mains cables.

ƒ

Connect the shield on the mains cables at both ends of the cable to the

mounting plate using large area connections.

Earthing
Drive actuator and RFI filter are metallic and conductive and must be earthed.

ƒ

Connect all metal, conductive components to a central earthing point.

ƒ

For the wiring use the minimum cross-section specified in the safety

regulations.

Layout

Note!

For EMC it is not the cable cross-section that is of importance, but

the size of the contact area between the drive controller, RFI filter

and mains choke and the earthed mounting plate.

The use of electrically conductive mounting plates (e.g. zinc-coated) ensures a

permanent safe contact.

ƒ

Remove the paint from the mounting areas if you use painted mounting

plates.

ƒ

Connect mounting plates e.g. together using copper strips and large area

connections if you use several mounting plates.

ƒ

Connect the shields correctly.